General specifications |
---|
Slave type | Standard slave |
AS-Interface specification | V3.0 |
Required master specification | ≥ V2.0 |
UL File Number | E223772 |
Functional safety related parameters |
---|
MTTFd | 150 a |
Mission Time (TM) | 20 a |
Diagnostic Coverage (DC) | 0 % |
Indicators/operating means |
---|
LED PWR/FAULT | dual LED green/red green: AS-Interface voltage red: communication error or address 0 green/red flashing: overload sensor supply or outputs |
LED AUX | ext. auxiliary voltage UAUX ; LED green |
LED IN | switching state (input); 4 LED yellow |
LED OUT | Switching state (output); 4 LED yellow |
Electrical specifications |
---|
Auxiliary voltage (output) | 24 V DC ± 15 % PELV |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
Rated operating current | ≤ 30 mA (without sensors) / max. 230 mA |
Protection class | III |
Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) |
Input |
---|
Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC |
Supply | from AS-Interface |
Voltage | 21 ... 31 V |
Current loading capacity | ≤ 200 mA (TB ≤ 40 °C), ≤ 160 mA (TB ≤ 60 °C), short-circuit protected |
Input current | ≤ 9 mA (limited internally) |
Switching point | according to DIN EN 61131-2 (Type 2) |
| 0 (unattenuated) | ≤ 3 mA |
| 1 (attenuated) | ≥ 5 mA |
Output |
---|
Number/Type | 4 electronic outputs, PNP, overload and short-circuit proof |
Supply | from external auxiliary voltage UAUX |
Current | 1 A per output, 4 A total |
Voltage | ≥ (UAUX - 0.5 V) |
Compliance with standards and directives |
---|
Directive conformity | |
| EMC Directive 2004/108/EC | EN 61000-6-2:2005, EN 61000-6-4:2007, EN 50295:1999 |
Standard conformity | |
| Noise immunity | EN 61000-6-2:2005, EN 50295:1999 |
| Emitted interference | EN 61000-6-4:2007 |
| Input | EN 61131-2:2007 |
| Degree of protection | EN 60529:2000 |
| Fieldbus standard | EN 50295:1999, IEC 62026-2:2006 |
Programming instructions |
---|
Profile | S-7.0 |
IO code | 7 |
ID code | 0 |
ID1 code | F |
ID2 code | E |
Data bits (function via AS-Interface) | input output |
| D0 | IN1 OUT1 |
| D1 | IN2 OUT2 |
| D2 | IN3 OUT3 |
| D3 | IN4 OUT4 |
Parameter bits (programmable via AS-i) | function |
| P0 | communication monitoring P0 = 1 (default settings), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition |
| P1 | not used |
| P2 | not used |
| P3 | not used |
Ambient conditions |
---|
Ambient temperature | -25 ... 60 °C (-13 ... 140 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Relative humidity | 85 % , noncondensing |
Climatic conditions | For indoor use only |
Altitude | ≤ 2000 m above MSL |
Pollution degree | 3 |
Mechanical specifications |
---|
Degree of protection | IP65 |
Connection | cable piercing method or terminal compartment yellow flat cable/black flat cable or standard round cable inputs/outputs:M12 x 1.5 cable glands and cage tension spring terminals |
Material | |
| Housing | PA 6 GF30 |
Mass | 350 g |
Tightening torque, housing screws | 0.8 Nm |
Mounting | DIN rail or screw mounting |